HY Island Express · Electrical
SIM-V010 · Ro-Pax Ferry · 28 installed systems
Simulation data · Read-only monitoring
VESSEL SYSTEM
Electrical
4 installed equipment · 0 running
Healthy0 active alertsLast telemetry 0.7s ago
MSB A active power2.57 MWGood
MSB B active power2.47 MWGood
MSB A insulation resistance777.0 kΩGood
ENERGY DISTRIBUTION
Monitoring onlyElectrical single-line
INSTALLED ASSETS
4 equipmentEquipment status
| Equipment | State | Primary measurement | Secondary |
|---|---|---|---|
| Main Switchboard AMSB-A | Standby | Voltage 6,900.0 V | Current 234.2 A |
| Main Switchboard BMSB-B | Standby | Voltage 6,900.0 V | Current 225.0 A |
| Bus Tiebus-tie | Standby | — | — |
| Shore Connectionshore-connection | Standby | Voltage 0.0 V | Frequency 0.0 Hz |
ENGINEERING MEASUREMENTS
119 pointsMeasurements
| Measurement | Equipment | Value | Data Quality | Updated |
|---|---|---|---|---|
| Voltageelec.msb_a.voltage_v | Main Switchboard A | 6,900.0 V | Good | 0.7s ago |
| Currentelec.msb_a.current_a | Main Switchboard A | 234.2 A | Good | 0.7s ago |
| Frequencyelec.msb_a.frequency_hz | Main Switchboard A | 50.0 Hz | Good | 0.7s ago |
| Active powerelec.msb_a.active_power_kw | Main Switchboard A | 2.57 MW | Good | 0.7s ago |
| Reactive powerelec.msb_a.reactive_power_kvar | Main Switchboard A | 515.0 kvar | Good | 0.7s ago |
| Power factorelec.msb_a.power_factor | Main Switchboard A | 0.9 ratio | Good | 0.7s ago |
| Thdelec.msb_a.thd_pct | Main Switchboard A | 2.6 % | Good | 0.7s ago |
| Insulation Resistanceelec.msb_a.insulation_resistance_kohm | Main Switchboard A | 777.0 kΩ | Good | 0.7s ago |
| Voltageelec.msb_b.voltage_v | Main Switchboard B | 6,900.0 V | Good | 0.7s ago |
| Currentelec.msb_b.current_a | Main Switchboard B | 225.0 A | Good | 0.7s ago |
| Frequencyelec.msb_b.frequency_hz | Main Switchboard B | 50.0 Hz | Good | 0.7s ago |
| Active powerelec.msb_b.active_power_kw | Main Switchboard B | 2.47 MW | Good | 0.7s ago |
| Reactive powerelec.msb_b.reactive_power_kvar | Main Switchboard B | 494.8 kvar | Good | 0.7s ago |
| Power factorelec.msb_b.power_factor | Main Switchboard B | 0.9 ratio | Good | 0.7s ago |
| Thdelec.msb_b.thd_pct | Main Switchboard B | 2.2 % | Good | 0.7s ago |
| Insulation Resistanceelec.msb_b.insulation_resistance_kohm | Main Switchboard B | 865.5 kΩ | Good | 0.7s ago |
| Closedelec.bus_tie.closed | Distribution | Active | Good | 0.7s ago |
| Voltageelec.esb.voltage_v | Distribution | 440.0 V | Good | 0.7s ago |
| Frequencyelec.esb.frequency_hz | Distribution | 50.0 Hz | Good | 0.7s ago |
| Availableelec.emergency_generator.available | Distribution | Active | Good | 0.7s ago |
| Availableelec.shore.available | Distribution | Inactive | Good | 0.7s ago |
| Connectedelec.shore.connected | Distribution | Inactive | Good | 0.7s ago |
| Voltageelec.dc24.voltage_v | Distribution | 26.2 V | Good | 0.7s ago |
| Loadelec.ups.load_pct | Distribution | 42.7 % | Good | 0.7s ago |
| Batteryelec.ups.battery_pct | Distribution | 94.0 % | Good | 0.7s ago |
| Breaker Closedelec.feeder.01.breaker_closed | Hotel Load | Active | Good | 0.7s ago |
| Currentelec.feeder.01.current_a | Hotel Load | 1,488.2 A | Good | 0.7s ago |
| Active powerelec.feeder.01.active_power_kw | Hotel Load | 3.08 MW | Good | 0.7s ago |
| Loadelec.feeder.01.load_pct | Hotel Load | 56.4 % | Good | 0.7s ago |
| Tripelec.feeder.01.trip | Hotel Load | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.01.quality | Hotel Load | Active | Good | 0.7s ago |
| Breaker Closedelec.feeder.02.breaker_closed | HVAC | Active | Good | 0.7s ago |
| Currentelec.feeder.02.current_a | HVAC | 1,200.0 A | Good | 0.7s ago |
| Active powerelec.feeder.02.active_power_kw | HVAC | 2.80 MW | Good | 0.7s ago |
| Loadelec.feeder.02.load_pct | HVAC | 45.9 % | Good | 0.7s ago |
| Tripelec.feeder.02.trip | HVAC | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.02.quality | HVAC | Active | Good | 0.7s ago |
| Breaker Closedelec.feeder.03.breaker_closed | Galley | Active | Good | 0.7s ago |
| Currentelec.feeder.03.current_a | Galley | 1,333.7 A | Good | 0.7s ago |
| Active powerelec.feeder.03.active_power_kw | Galley | 3.47 MW | Good | 0.7s ago |
| Loadelec.feeder.03.load_pct | Galley | 47.4 % | Good | 0.7s ago |
| Tripelec.feeder.03.trip | Galley | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.03.quality | Galley | Active | Good | 0.7s ago |
| Breaker Closedelec.feeder.04.breaker_closed | Fresh Water Tank | Active | Good | 0.7s ago |
| Currentelec.feeder.04.current_a | Fresh Water Tank | 1,160.9 A | Good | 0.7s ago |
| Active powerelec.feeder.04.active_power_kw | Fresh Water Tank | 2.68 MW | Good | 0.7s ago |
| Loadelec.feeder.04.load_pct | Fresh Water Tank | 58.4 % | Good | 0.7s ago |
| Tripelec.feeder.04.trip | Fresh Water Tank | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.04.quality | Fresh Water Tank | Active | Good | 0.7s ago |
| Breaker Closedelec.feeder.05.breaker_closed | Sewage Plant | Active | Good | 0.7s ago |
| Currentelec.feeder.05.current_a | Sewage Plant | 1,284.1 A | Good | 0.7s ago |
| Active powerelec.feeder.05.active_power_kw | Sewage Plant | 2.72 MW | Good | 0.7s ago |
| Loadelec.feeder.05.load_pct | Sewage Plant | 47.7 % | Good | 0.7s ago |
| Tripelec.feeder.05.trip | Sewage Plant | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.05.quality | Sewage Plant | Active | Good | 0.7s ago |
| Breaker Closedelec.feeder.06.breaker_closed | Propulsion Motor | Active | Good | 0.7s ago |
| Currentelec.feeder.06.current_a | Propulsion Motor | 1,390.7 A | Good | 0.7s ago |
| Active powerelec.feeder.06.active_power_kw | Propulsion Motor | 3.42 MW | Good | 0.7s ago |
| Loadelec.feeder.06.load_pct | Propulsion Motor | 59.5 % | Good | 0.7s ago |
| Tripelec.feeder.06.trip | Propulsion Motor | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.06.quality | Propulsion Motor | Active | Good | 0.7s ago |
| Breaker Closedelec.feeder.07.breaker_closed | Hotel Load | Active | Good | 0.7s ago |
| Currentelec.feeder.07.current_a | Hotel Load | 1,125.7 A | Good | 0.7s ago |
| Active powerelec.feeder.07.active_power_kw | Hotel Load | 3.04 MW | Good | 0.7s ago |
| Loadelec.feeder.07.load_pct | Hotel Load | 58.8 % | Good | 0.7s ago |
| Tripelec.feeder.07.trip | Hotel Load | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.07.quality | Hotel Load | Active | Good | 0.7s ago |
| Breaker Closedelec.feeder.08.breaker_closed | HVAC | Active | Good | 0.7s ago |
| Currentelec.feeder.08.current_a | HVAC | 1,126.1 A | Good | 0.7s ago |
| Active powerelec.feeder.08.active_power_kw | HVAC | 3.56 MW | Good | 0.7s ago |
| Loadelec.feeder.08.load_pct | HVAC | 59.5 % | Good | 0.7s ago |
| Tripelec.feeder.08.trip | HVAC | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.08.quality | HVAC | Active | Good | 0.7s ago |
| Breaker Closedelec.feeder.09.breaker_closed | Galley | Active | Good | 0.7s ago |
| Currentelec.feeder.09.current_a | Galley | 1,384.8 A | Good | 0.7s ago |
| Active powerelec.feeder.09.active_power_kw | Galley | 3.39 MW | Good | 0.7s ago |
| Loadelec.feeder.09.load_pct | Galley | 57.2 % | Good | 0.7s ago |
| Tripelec.feeder.09.trip | Galley | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.09.quality | Galley | Active | Good | 0.7s ago |
| Breaker Closedelec.feeder.10.breaker_closed | Fresh Water Tank | Active | Good | 0.7s ago |
| Currentelec.feeder.10.current_a | Fresh Water Tank | 1,483.4 A | Good | 0.7s ago |
| Active powerelec.feeder.10.active_power_kw | Fresh Water Tank | 3.45 MW | Good | 0.7s ago |
| Loadelec.feeder.10.load_pct | Fresh Water Tank | 52.9 % | Good | 0.7s ago |
| Tripelec.feeder.10.trip | Fresh Water Tank | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.10.quality | Fresh Water Tank | Active | Good | 0.7s ago |
| Breaker Closedelec.feeder.11.breaker_closed | Sewage Plant | Active | Good | 0.7s ago |
| Currentelec.feeder.11.current_a | Sewage Plant | 1,272.9 A | Good | 0.7s ago |
| Active powerelec.feeder.11.active_power_kw | Sewage Plant | 3.10 MW | Good | 0.7s ago |
| Loadelec.feeder.11.load_pct | Sewage Plant | 49.0 % | Good | 0.7s ago |
| Tripelec.feeder.11.trip | Sewage Plant | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.11.quality | Sewage Plant | Active | Good | 0.7s ago |
| Breaker Closedelec.feeder.12.breaker_closed | Propulsion Motor | Active | Good | 0.7s ago |
| Currentelec.feeder.12.current_a | Propulsion Motor | 1,387.1 A | Good | 0.7s ago |
| Active powerelec.feeder.12.active_power_kw | Propulsion Motor | 2.91 MW | Good | 0.7s ago |
| Loadelec.feeder.12.load_pct | Propulsion Motor | 48.5 % | Good | 0.7s ago |
| Tripelec.feeder.12.trip | Propulsion Motor | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.12.quality | Propulsion Motor | Active | Good | 0.7s ago |
| Breaker Closedelec.feeder.13.breaker_closed | Hotel Load | Active | Good | 0.7s ago |
| Currentelec.feeder.13.current_a | Hotel Load | 1,491.0 A | Good | 0.7s ago |
| Active powerelec.feeder.13.active_power_kw | Hotel Load | 3.10 MW | Good | 0.7s ago |
| Loadelec.feeder.13.load_pct | Hotel Load | 50.2 % | Good | 0.7s ago |
| Tripelec.feeder.13.trip | Hotel Load | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.13.quality | Hotel Load | Active | Good | 0.7s ago |
| Breaker Closedelec.feeder.14.breaker_closed | HVAC | Active | Good | 0.7s ago |
| Currentelec.feeder.14.current_a | HVAC | 1,418.1 A | Good | 0.7s ago |
| Active powerelec.feeder.14.active_power_kw | HVAC | 3.38 MW | Good | 0.7s ago |
| Loadelec.feeder.14.load_pct | HVAC | 50.0 % | Good | 0.7s ago |
| Tripelec.feeder.14.trip | HVAC | Inactive | Good | 0.7s ago |
| Qualityelec.feeder.14.quality | HVAC | Active | Good | 0.7s ago |
| Apparent powerelec.msb_a.extended.apparent_power_kva | Main Switchboard A | 2,710.4 kVA | Good | 0.7s ago |
| Current THDelec.msb_a.extended.thd_current_pct | Main Switchboard A | 3.2 % | Good | 0.7s ago |
| Loadelec.msb_a.extended.load_pct | Main Switchboard A | 78.5 % | Good | 0.7s ago |
| Apparent powerelec.msb_b.extended.apparent_power_kva | Main Switchboard B | 2,604.1 kVA | Good | 0.7s ago |
| Current THDelec.msb_b.extended.thd_current_pct | Main Switchboard B | 2.7 % | Good | 0.7s ago |
| Loadelec.msb_b.extended.load_pct | Main Switchboard B | 75.4 % | Good | 0.7s ago |
| Voltageelec.shore.extended.voltage_v | Shore Connection | 0.0 V | Good | 0.7s ago |
| Frequencyelec.shore.extended.frequency_hz | Shore Connection | 0.0 Hz | Good | 0.7s ago |
| Breaker Closedelec.shore.extended.breaker_closed | Shore Connection | Inactive | Good | 0.7s ago |
| Synchronization stateelec.shore.extended.synchronized | Shore Connection | Inactive | Good | 0.7s ago |